Plant Optimization Sprints.
Fixed-price BMS optimization for specific plant systems, delivered in 4-8 weeks with 90-day IPMVP-compliant M&V. No capex, no downtime, no new equipment. Five sprint types cover Steam, Hot Water, Chilled Water, Condenser Water, and Air Handlers. Typical range: 12-22% utility spend reduction on buildings with drifted BMS.
Pick the plant. We drive it back to design intent.
Steam Plant Optimization
Header pressure reset, boiler staging, condensate return, trap survey. Header pressure alone typically drives 5-10% therms reduction.
- Boiler setpoint & staging review
- OAT-based header pressure reset schedule
- Steam trap survey (visual + ultrasonic)
- Condensate return optimization
- Deaerator, blowdown, feedwater review
- Combustion air trim (if BMS-controlled)
Hot Water System Optimization
OAT-based reset, preheat/reheat separation, pump VFD tuning. HW reset alone typically drives 10-20% therms/kWh reduction.
- HWS setpoint + OAT-based reset schedule
- Preheat/reheat loop separation validation
- Pump lead-lag + VFD tuning, DP reset
- Deadband analysis (fighting valves)
- Boiler/heat exchanger staging
- Bypass valve setpoint review
Chilled Water Plant Optimization
CHW reset, chiller staging, pump DP reset, primary/secondary loop optimization. Every 1°F CHW increase = ~1.5% chiller kW reduction.
- CHW supply setpoint + reset schedule
- Chiller staging + lead-lag sequencing
- CHW pump VFD tuning + DP reset
- Primary/secondary/tertiary loop optimization
- Free cooling / waterside economizer integration
- Turndown limits vs. actual load profile
Condenser Water Optimization
CW reset, tower fan staging, approach control, free cooling changeover. Lower CW supply = higher chiller COP.
- CW supply temperature setpoint + reset schedule
- Tower fan staging + VFD control
- CW approach temperature target validation
- Free cooling changeover setpoint
- Basin blowdown + makeup control
- Multi-cell tower rotation logic
AHU Optimization
Static pressure reset, DCV, economizer tuning, minimum OA validation. Static pressure alone typically drives 15-30% supply fan kW reduction.
- Discharge air temperature + reset schedule
- Supply fan static pressure reset (trim-and-respond)
- Demand-controlled ventilation (CO2 or occupancy)
- Economizer changeover setpoint + operation
- Unoccupied setback / setup schedules
- Minimum outside air validation
Universal deliverables
- Baseline consumption report (pre-implementation)
- Findings & recommendations memo
- Change log with rationale for every setpoint/sequence change
- Post-implementation M&V report per IPMVP Option B or C with verified savings
- Operator handoff documentation
Not included in Sprint scope
- ×Capex equipment or new controls hardware
- ×Structural or mechanical retrofits
- ×24/7 ongoing monitoring beyond the 90-day M&V window (M&V Retainer covers this)
4-8 weeks to implementation. 90 days to verified savings.
Questions owners ask before signing.
Do we need a Rapid Diagnostic before a Sprint?+
Which sprint should we start with?+
What's the 90-day M&V window for?+
Can we bundle multiple sprints?+
What if the sprint doesn't save what you projected?+
What if we have an unusual BMS vendor?+
Do you handle Plant Optimization for hospitals?+
How does this relate to LL87 retro-commissioning?+
Start with a free 30-min intake call.
We walk your building context, confirm which sprint fits, and scope pricing. If a diagnostic is the right first step, we say so and route you to the $2,500 Rapid Diagnostic instead.